article
This paper demonstrates voltage profile improvement by partitioning the Y-admittance and the application of circuit theory on power system networks. The partitioned Y-admittance matrix and eigenvalue decomposition technique were used to identify the suitable locations for reactive power compensators. The proposed approach was applied to the 40-bus Southwest England network and the results were compared with the classical Q-V sensitivity approach. The proposed approach improves the overall voltage profile towards the nominal voltage limit.
This page summarises published work. The authoritative version sits with the publisher.
DOI: 10.1109/tdc-la.2012.6319054
Is something wrong with this record? Report it or request removal.
Discussion
Have you built on this work, tried to replicate it, or seen it applied in practice? Share what you know. Verified researchers and MARATTO™ domain experts can open a discussion, and any member can reply. Contributions are reviewed before they appear.
No discussion yet. Open the first thread.
New to MARATTO™? Create a free account.