article
To suppress the resonance in LCL-type grid-connected inverter (GCI), various active damping (AD) methods have been developed. In this article, an inverter-side current feedback active damping (ICFB-AD) strategy with phase-lead compensation is proposed, which achieves both resonance attenuation and accurate current control. A second-order unstable phase-lead filter is introduced in series with the ICFB loop to enhance the stability and robustness of the GCI. Design guidelines for the second-order unstable PLF are also presented. The proposed system ensures stability across a wide range of LCL resonance frequencies and exhibits strong robustness against variations in the filter inductance and grid impedance. Finally, the effectiveness of the proposed ICFB-AD strategy, along with its z-domain design methodology, is validated by experimental results.
This page summarises published work. The authoritative version sits with the publisher.
DOI: 10.1109/cpere65146.2025.11240016
Is something wrong with this record? Report it or request removal.
Discussion
Have you built on this work, tried to replicate it, or seen it applied in practice? Share what you know. Verified researchers and MARATTO™ domain experts can open a discussion, and any member can reply. Contributions are reviewed before they appear.
No discussion yet. Open the first thread.
New to MARATTO™? Create a free account.