MARATTO

article · World Journal of Engineering and Technology

Contribution to Asymmetrical Compensation through Parallel Controllers of FACTS (STATCOM)—IPC 240 Dual for a Power Transmission Line

20232 citationsOpen accessUniversity of Douala

Abstract

This work is part of the resolution of problems encountered on a 225 KV MANGOMBE-OYOMABANG line. This line is characterized by important technical losses, so that the voltage injected in the busbar is always lower than 200kV. The main objective of this work is to show the new solutions that can provide a combined FACTS-STATCOM and IPC 240 dual system on this line. Then to show the limitation of STATCOM compared to RPI 240. The results obtained allowed us to observe that in symmetrical operation the STATCOM improves the voltage profile on the busbar and in asymmetrical operation we found that it continues to regulate the voltage of each phase despite the unbalance. But the system remains too unbalanced because of the sequence current flow. The IPC 240 corrects this limitation, allowing asymmetrical operation of the line in an emergency while providing continuous service to the load.

Research topics

  • Thermal Analysis in Power Transmission
  • Power System Reliability and Maintenance
  • Power System Optimization and Stability

Sustainable Development Goals

Read the original research

This page summarises published work. The authoritative version sits with the publisher.

DOI: 10.4236/wjet.2023.111003

Is something wrong with this record? Report it or request removal.

Discussion

Discuss this research

Have you built on this work, tried to replicate it, or seen it applied in practice? Share what you know. Verified researchers and MARATTO™ domain experts can open a discussion, and any member can reply. Contributions are reviewed before they appear.

No discussion yet. Open the first thread.